AC / DC Voltage Drop & Cable Sizing Calculator

Size electrical conductors accurately by calculating line impedance, resistance, percentage voltage drop across long runs, and compliance with the 3% branch circuit standard.

Circuit Parameters

Voltage Drop (% ΔV)
2.82%
End Voltage
388.7 V

Calculation Steps

1. Conductor Line Resistance (R)

Based on copper resistivity at operating temperature (0.0214 \(\Omega\cdot\text{mm}^2/\text{m}\)).

2. Total Voltage Drop (\Delta V)

Calculated with power factor \(\cos\phi = 0.88\).

3. Terminal Voltage & Cable Heating Power Loss

Joule $I^2 R$ heat dissipated into the raceway/tray.

Official Review

Preparing for the FE Electrical & PE Power Exam Course?

Study with the industry standard: PPI2Pass PE Power Comprehensive Review by John A. Camara, PE.

NEC 2023 / NFPA 70 Code Focus 3-Phase Power & Protection Calculations Step-by-Step Diagnostic Exams
Explore PPI2Pass Courses* Official Kaplan Partner Program

Governing Equation

Analytical equations compliant with standard university curricula and professional engineering practice codes.

Engineering Reference & Technical Guide

AC & DC Voltage Drop and Cable Sizing Engineering Reference Guide

Peer-reviewed mathematical formulation, verified step-by-step worked engineering calculations, design codes, and practical guidelines.

Governing Theory & Derivation

Analytical physics and classical mechanics foundations

Electrical current flowing through conductors experiences voltage loss proportional to conductor resistance and inductive reactance. Excessive voltage drop reduces motor starting torque, causes lighting flicker, overheats insulation, and violates National Electrical Code (NEC) standards.

1. Three-Phase AC Voltage Drop

For three-phase balanced systems taking power factor into account:

2. Single-Phase AC and DC Voltage Drop

In single-phase two-wire circuits, current traverses both out-and-return conductors (distance × 2):

3. Percentage Voltage Drop and Code Limits

Expressed as a percentage of nominal service supply voltage V_n:

Engineering Interpretation:Inductive reactance (X) is caused by the alternating electromagnetic field surrounding conductors. For large wire gauges (> 100 mm² or 4/0 AWG), inductive reactance often exceeds pure ohmic resistance.

Step-by-Step Worked Example

480V 3-Phase Industrial Feeder Cable Sizing

Problem Statement

A 480V, 3-phase, 60 Hz balanced industrial sub-panel carries a design load of I = 120 Amperes at 0.85 lagging power factor. The one-way distance from the main switchboard is L = 150 meters (492 ft). Copper conductors in steel conduit are used. Check if 50 mm² (approx. 1/0 AWG) copper conductor (R = 0.493 Ω/km, X = 0.155 Ω/km) satisfies the NEC 3% voltage drop limit.

Given Parameters

System Voltage (V_n)480 V (3-Phase)
Design Current (I)120 A
Feeder Length (L)150 m (0.15 km)
Power Factor (cos φ)0.85 lagging (sin φ = 0.5268)
Conductor Resistance (R)0.493 Ω/km
Inductive Reactance (X)0.155 Ω/km

Detailed Calculation Steps

1Compute Effective Conductor Impedance

Combines real resistive and reactive AC impedance components.

2Calculate Line-to-Line Voltage Drop

Line-to-line voltage loss over the 150 m feeder run.

3Calculate Percentage Drop and Compare to NEC 3% Criterion

Exceeds the 3.0% maximum branch circuit limit recommended by NEC 210.19(A).

Conclusion & Design Verification:Because 3.25% exceeds the 3% limit, upsize conductor to 70 mm² (approx. 2/0 AWG, R = 0.342 Ω/km), which yields a compliant 2.38% voltage drop.

Applicable Standards & Design Codes

Recognized engineering guidelines and criteria

NEC 210.19(A) & 215.2(A)NFPA

National Electrical Code (NFPA 70)

Recommends maximum 3% drop on branch circuits or feeders, and 5% total overall.

IEC 60364-5-52IEC

Low Voltage Electrical Installations - Wiring Systems

Specifies 3% limit for lighting and 5% for general power.

Assumptions & Practical Limitations

Critical constraints for professional applications

  • Temperature rises under heavy load increase copper resistance by approx. 0.393% per °C (check ampacity temperature derating per NEC 310.16).
  • Steel conduits increase inductive reactance compared to PVC conduits due to magnetic eddy current effects.
  • Check motor starting inrush current (typically 5-7× full load amps) to ensure starting voltage drop remains below 10-15% to prevent motor stalling.

Frequently Asked Questions

Common technical engineering inquiries

Q:Why does lagging power factor affect voltage drop?

Inductive loads (motors, transformers) draw lagging reactive current. When reactive current flows through cable inductive reactance (X·sin φ), it directly reduces terminal voltage.

Q:What is the difference between ampacity sizing and voltage drop sizing?

Ampacity sizing protects conductor insulation from overheating and melting. Voltage drop sizing ensures equipment receives adequate operating voltage over long transmission distances. Long circuits are almost always governed by voltage drop rather than ampacity.